Adjust motor current monitoring
The minimum and maximum motor current of the connected pumps is monitored:
- Minimum motor current monitoring
- The value is permanently stored in the switchgear: 300 mA or 10% of the set motor current.
- Maximum motor current monitoring
- Adjust the value in the switchgear.
Monitoring of the maximum motor current is carried out via electronic motor current monitoring.
The same potentiometers are used for switchgears up to 12 A and up to 23 A: scale 0 to 12. The following applies to the adjustment of the rated currents:
- Switchgears up to 12 A: The value corresponds 1:1 to the scale, e.g. 6 = 6 A. Maximum adjustable value: 12 A
- Switchgears up to 23 A: The value corresponds 1:2 to the scale, e.g. 6 = 12 A. Maximum adjustable value: 24 A
After connecting the pumps, set the rated motor current of the pump.
8 | Potentiometer for motor current monitoring |
Use a screwdriver to set the rated motor current at the respective potentiometer.
Precise adjustment of motor current monitoring can be performed during commissioning. During commissioning, the set and the actual rated motor current can be shown on the display:
- Currently set value of the motor current monitoring (Menu 4.25 – 4.26)
- Currently measured operating current of the pump (Menu 4.29 – 4.30)