Switchgear mains connection

DANGER

danger

Danger of death due to electrical current when the main switch is switched off!

Even when the main switch is switched off, there is mains voltage power to the voltage selection terminal.

  1. Make the voltage selection before connecting the product to the mains.

CAUTION

Risk of property damage due to incorrectly set mains voltage!

If the wrong mains voltage is set, the switchgear will be destroyed. The switchgear can be operated at different mains voltages. The mains voltage is set to 400 V at the factory.

  1. To use another mains voltage, change the position of the cable jumper before connection.

Mains connection Wilo-Control EC-WP 1 …/EC-WP 2 … up to 12 A

1

Terminal strip: Mains connection

2

Mains voltage adjustment

3

Terminal strip: Earth (PE)

Insert the connection cable laid by the customer through the threaded cable glands and secure it. Connect the wires to the terminal strip according to the connection diagram.

Mains connection 1~230 V:

  • Cable: 3-core
  • Wire: L, N, PE
  • Mains voltage adjustment: Converter bridge 230/COM

Mains connection 3~230 V:

  • Cable: 4-core
  • Wire: L1, L2, L3, PE
  • Mains voltage adjustment: Converter bridge 230/COM

Mains connection 3~380 V:

  • Cable: 4-core
  • Wire: L1, L2, L3, PE
  • Mains voltage adjustment: Converter bridge 380/COM

Mains connection 3~400 V:

  • Cable: 4-core
  • Wire: L1, L2, L3, PE
  • Mains voltage adjustment: Converter bridge 400/COM (factory setting)
Mains connection Wilo-Control EC-WP 1.../EC-WP 2...
Mains connection Wilo-Control EC-WP 1.../EC-WP 2...

Mains connection Wilo-Control EC-WP 1 … up to 23 A

NOTICE

notice

Neutral conductor required

A neutral conductor is required at the mains connection for the correct functioning of the controls.

1

Terminal strip: Mains connection

2

Mains voltage adjustment

3

Terminal strip: Earth (PE)

Insert the connection cable laid by the customer through the threaded cable glands and secure it. Connect the wires to the main switch as per connection diagram.

Mains connection 3~230 V:

  • Cable: 5-core
  • Wire: L1, L2, L3, N, PE
  • Mains voltage adjustment: Converter bridge 230/COM

Mains connection 3~380 V:

  • Cable: 5-core
  • Wire: L1, L2, L3, N, PE
  • Mains voltage adjustment: Converter bridge 380/COM

Mains connection 3~400 V:

  • Cable: 5-core
  • Wire: L1, L2, L3, N, PE
  • Mains voltage adjustment: Converter bridge 400/COM (factory setting)
Mains connection Wilo-Control EC-WP 1… up to 23 A
Mains connection Wilo-Control EC-WP 1… up to 23 A