Pump kick
In order to avoid impeller/rotor blockages when the pump is at standstill for longer periods (e.g. an inactive heating system during summer), the pump regularly performs pump kicks by briefly starting it. In this process, it starts briefly.
If the pump does not start operating within an interval of 24 hours (factory setting), the system completes a pump kick. In this process, the pump must always be supplied with power. You can change the pump kick interval at the pump.
In the “Diagnostics and measured values” menu , select
- “Maintenance”
- “Pump kick” in sequence.
The pump kick can be switched on and off.
- Pumps with SW version (SW ≤ 01.04.):
- Time interval between 1 hour and 24 hours, factory setting: 24 h
- Pumps with SW version (SW ≥ 01.05.):
- Time interval between 2 hour and 72 hours, factory setting: 24 h