Configuration warnings

Configuration warnings occur if an incomplete or contradictory configuration has been made.

Example:
The “Hall temperature control” function requires a temperature sensor. The corresponding source is not specified or not correctly configured.

Configuration warnings

Code

Fault

Cause

Remedy

601

Setpoint source not suitably configured.

Setpoint is not connected to correct source. Input not suitably configured.

Configure source or
select another source.

The setpoint source is not correctly configured. In the context menu there is a link for configuring the setpoint source.

602

Setpoint source not available.

Setpoint not connected to existing CIF module.

Insert CIF module.
Activate CIF module.

The setpoint source or the CIF module is not correctly configured. In the context menu there are links for configuration.

603

Sensor source not suitably configured.

Sensor 1 is not connected to correct source. Input not suitably configured.

Configure source.
Select other source.

The sensor source is not correctly configured. In the context menu there is a link for configuring the sensor source.

604

Same sensor source not possible.

Sensor sources are configured to the same source.

Configure a sensor source to another source.

The sensor sources are not correctly configured. In the context menu there is a link for configuring the sensor sources.

606

Sensor source not available.

Sensor value 1 is not connected to existing CIF module.

Insert CIF module.
Activate CIF module.

The sensor source or the CIF module is not correctly configured. In the context menu there are links for configuration.

607

Sensor source not suitably configured.

Sensor 2 is not connected to correct source. Input not suitably configured.

Configure source or
select another source.

The sensor source is not correctly configured. In the context menu there is a link for configuring the sensor source.

609

Sensor source not available.

Sensor value 2 is not connected to existing CIF module.

Insert CIF module.
Activate CIF module.

The sensor source or the CIF module is not correctly configured. In the context menu there are links for configuration.

610

Sensor source not suitably configured.

Feed temperature sensor is not connected to correct source. Input not suitably configured.

Configure source to “temperature sensor” usage type or select another source.

The sensor source is not correctly configured. In the context menu there is a link for configuring the sensor source.

611

Same sensor source not possible.

Sensor sources for heat meter configured for the same source.

Configure one of the sensor sources for the heat meter to another source.

The sensor sources are not correctly configured. In the context menu there is a link for configuring the sensor sources.

614

Sensor source not available.

Feed temperature is not connected to existing CIF module.

Insert CIF module.
Activate CIF module.

The sensor source or the CIF module is not correctly configured. In the context menu there are links for configuration.

615

Sensor source not suitably configured.

Return temperature sensor is not connected to correct source. Input not suitably configured.

Configure source to “temperature sensor” usage type or select another source.

The sensor source is not correctly configured. In the context menu there is a link for configuring the sensor source.

618

Sensor source not available.

Return temperature is not connected to existing CIF module.

Insert CIF module.
Activate CIF module.

The sensor source or the CIF module is not correctly configured. In the context menu there are links for configuration.

619

Sensor source not suitably configured.

Temperature sensor for “Heating/cooling switchover” is not connected to the correct source. Input not suitably configured.

Configure source to “temperature sensor” usage type or select another source.

The sensor source is not correctly configured. In the context menu there is a link for configuring the sensor source.

621

Sensor source not available.

Temperature value for “Heating/cooling switchover” is not connected to existing CIF module.

Insert CIF module.
Activate CIF module.

The sensor source or the CIF module is not correctly configured. In the context menu there are links for configuration.

641

Setpoint source not suitably configured.

Setpoint is not connected to correct source. Input not suitably configured.

Configure source or
select another source.

The setpoint source for the cooling function is not correctly configured. In the context menu there is a link for configuring the setpoint source.

642

Setpoint source not available.

Setpoint not connected to existing CIF module.

Insert CIF module.
Activate CIF module.

The setpoint source for the cooling function or the CIF module is not correctly configured. In the context menu there are links for configuration.

643

Sensor source not suitably configured.

Sensor 1 is not connected to correct source. Input not suitably configured.

Configure source.
Select other source.

The sensor source for the cooling function is not correctly configured. In the context menu there is a link for configuring the sensor source.

644

Same sensor source not possible.

Sensor sources are configured to the same source.

Configure a sensor source to another source.

The sensor sources for the cooling function are not correctly configured. In the context menu there is a link for configuring the sensor sources.

646

Sensor source not available.

Sensor value is not connected to existing CIF module.

Insert CIF module.
Activate CIF module.

The sensor source or the CIF module is not correctly configured. In the context menu there are links for configuration.

647

Sensor source not suitably configured.

Sensor 2 is not connected to correct source. Input not suitably configured.

Configure source or
select another source.

The sensor source for the cooling function is not correctly configured. In the context menu there is a link for configuring the sensor source.

649

Sensor source not available.

Sensor value 2 is not connected to existing CIF module.

Insert CIF module.
Activate CIF module.

The sensor source or the CIF module is not correctly configured. In the context menu there are links for configuration.

650

No MFA1) partner pump

MFA1) is selected, but no partner pump is configured.

Configuration of MFA1) partner pumps is required or select another control mode.

MFA1) collects the requirement of configured partner pumps to supply in total. For this purpose, the partner pumps must be selected in the MFA1) configuration.

1)MFA= Multi-Flow Adaptation