SSM/SBM relay forced control

An SSM/SBM relay forced control is used as function test of the SSM/SBM relay and electrical connections.

In the “Diagnostics and measured values” menu , select

  1. “Diagnostics help”
  2. “SSM relay forced control” or “SBM relay forced control” in sequence.

Selection options:

Selection option SSM/SBM relay forced control

SSM/SBM relay

Forced control

Help text

Normal

SSM: Depending on the SSM configuration, fault and warnings influence the SSM relay switching status.

SBM: Depending on the SBM configuration, the pump status influences the SBM relay switching status.

Forced active

SSM/SBM relay switching status is forced ACTIVE.

CAUTION:
SSM/SBM does not display the pump status!

Forced inactive

SSM/SBM relay switching status is forced INACTIVE.

CAUTION:
SSM/SBM does not display the pump status!

The “Forced active” setting permanently activates the relay. A warning/operating note (light) is permanently displayed/indicated.
The “Forced inactive” setting leaves the relay permanently without a signal. No warning/operating note can be confirmed.