Application and function of SSM relay

The contact of the collective fault signal (SSM, potential-free changeover contact) can be connected to a building automation system. The SSM relay can either switch on only in case of fault or for faults and warnings.

In the “Settings” menu , select

  1. “External interfaces”
  2. “SSM relay function”.

 

Possible settings:

Function SSM relay

Selection option

Function SSM relay

Only fault (factory setting)

SSM relay connects only in case of fault. Fault means: The pump is not running.

Faults and warnings

SSM relay connects only in case of fault or a warning.

After confirming one of the selection options, the SSM trigger delay and SSM reset delay are entered.

Trigger and reset delay

Setting

Range in seconds

SSM trigger delay

0 s … 60 s

SSM reset delay

0 s … 60 s

 

Trigger delays are used so that processes are not influenced by very short fault or warning messages.
If a fault or a warning is fixed before the end of the set time, there will be no message to SSM.
A set SSM trigger delay of 0 seconds immediately reports faults or warnings.

If an error message or warning message occurs only for a brief duration (e.g. in case of a loose contact), the reset delay prevents the SSM signal from fluttering.

NOTICE

notice

SSM trigger and SSM reset delay is set to 5 seconds as a factory setting.