Setting “Detection of thermal disinfection”
Starting situation
- Pump starts in factory settings DA+.
- PT1000 B is connected to the analogue input AI1.
The following operating steps can be set via the menu using the control knob:
→ | Settings (turn control knob right + press) |
→ | Set control mode (press control knob) |
→ | Detection of disinfection (turn control knob right + press) |
→ | Switched on (turn control knob right + press) |
→ | Set disinfection limit value (press control knob) |
→ | Sensor detection of disinfection (turn control knob right + press) |
NOTICE
The factory setting for the temperature sensor of thermal disinfection is the analogue input AI1.
If necessary, this can be changed.
→ | Set sensor input (turn control knob right + press) |
→ | Select Temperature sensor for type of use at analogue input AI1 (turn control knob right + press) |
→ | Select PT1000 for signal type and analogue input AI1 for temperature sensor. (Press control knob) |
→Press and hold back button (left); the setting returns to the start screen.
NOTICE
The temperature measurements for the control mode T-c and for the disinfection detection cannot be taken with the same temperature sensor. In this case, the control mode switches to n-const. with the set emergency operation speed.