Setting two single pumps in dual-pump operation
Starting situation
- Pumps start in factory setting DA+.
- Both pumps are connected with a cable via the Wilo Net interface.
The following settings must be configured on both pumps:
→ | Settings (turn control knob right + press) |
→ | External interfaces (turn control knob right + press) |
→ | Wilo Net setting (turn control knob right + press) |
→ | Wilo Net termination (turn control knob left + press) |
→ | Switched on (press control knob) |
→ | Wilo Net address (turn control knob right + press) |
→ | Assign address 1 or 2 (press control knob) |
→Press and hold back button (left); the setting returns to the start screen.
Configure the settings on the second pump in the same way:
Set dual-pump operation:
The settings are only configured on the main pump:
→ | Settings (turn control knob right + press) |
→ | Dual-pump operation (turn control knob right + press) |
→ | Type of twin-head pump housing (turn control knob right + press) |
→ | Single pump (turn control knob left + press) |
→ | Connect twin-head pump (press control knob) |
→ | Select partner (turn control knob right + press) |
The partner is in “focus” and the blue LED display flashes.
→ | Confirmation on the main pump (press control knob) |
→ | Adopt configuration from this pump (press control knob) |
→ | Twin-head pump connection requires a restart (press control knob) |
NOTICE
Following the re-start, the blue LED displays on both pumps flash.
NOTICE
Settings on the twin-head pump can only be adjusted on pump 1 (main pump).
NOTICE
The display shows which dual-pump operation – peak-load operation () or main/standby operation () is active in the active influences area.
NOTICE
An “SL” symbol and the symbol for key lock also appear on the display of pump 2.