Setting “control mode T-c” including configuration of a PT1000 temperature sensor
Starting situation
- Pump starts in factory settings DA+.
- A PT1000 is, for example, connected to analogue input AI1.
The following operating steps can be set via the menu using the control knob:
→ | Settings (turn control knob right + press) |
→ | Set control mode (press control knob) |
→ | Setting assistant (press control knob) |
→ | e.g. heating (press control knob) |
→ | Fan heater (turn control knob right + press) |
→ | Hall temperature T-c (turn control knob right + press) |
→ | Sensor source T1 – analogue input 1 (turn control knob right + press) |
→ | Setpoint temperature T-c (turn control knob right + press) |
→ | Set setpoint temperature up to e.g. 25 °C (turn control knob right + press) |
→ | Temperature sensor T1 (turn control knob right + press) |
→ | Set sensor input up to e.g. 25 °C (turn control knob right + press) |
→ | Temperature sensor (turn control knob right + press) |
→ | PT1000 (press control knob) |
→Press and hold back button (left); the setting returns to the start screen.