Setting “External interfaces 0-10V”
Starting situation
- Pump starts in factory settings DA+.
- An external sensor is already connected to analogue input AI1 or analogue input AI2.
The following operating steps can be set via the menu using the control knob:
→ | Settings (turn control knob right + press) |
→ | Set control mode (press control knob) |
→ | Setting assistant (press control knob) |
→ | e.g. heating (press control knob) |
→ | Underfloor heating (turn control knob right + press) |
→ | Differential pressure Δp-c (press control knob) |
The setting returns to “Setting assistant”. Resume navigation.
→ | Setpoint delivery head (Press Context button + turn left + press) |
→ | External setpoint (turn control knob) |
Depending on assignment, select either analogue input AI1 or analogue input AI2 (turn control knob right + press).
→ | External setpoint source (turn control knob right + press) |
→ | Set setpoint source (turn control knob right + press) |
→ | Setpoint sensor (turn control knob right + press) |
→ | 0-10 V (press control knob) |
→ | e.g. use specification (press control knob) |
→Press and hold back button (left); the setting returns to the start screen.
The blue LED below the display lights up. The setpoint delivery head field in the display is marked with a blue frame, as is the display of the active analogue input (either analogue input AI1 or analogue input AI2).