Application and function of the analogue inputs AI1 and AI2

Analogue inputs can be used for setpoint input or actual value input. The allocation of setpoint and actual value specifications is freely configurable.

The type of use (setpoint sensor, differential pressure sensor, external sensor, etc.), the signal type (0 to 10 V, 0 to 20 mA, etc.) and the corresponding signal/value assignments are set via the menus “Function of analogue input AI1” and “Function analogue input AI2”. In addition, information about the current settings can be queried.

The analogue input is pre-defined for the required signal depending on the selected control mode of the pump.

In the “Settings” menu , select

  1. “External interfaces”
  2. External interfaces
  3. “Function analogue input AI1” or “Function analogue input AI2” in sequence.
Function analogue input

After selecting one of the options “Analogue input (AI1) function” or “Analogue input (AI2) function”, select the following query or setting:

Setting analogue input AI1 or AI2

Setting

Function control input AI1 or AI2

Overview of the analogue input

Overview of settings of this analogue input, for example:

• Type of use: Temperature sensor

• Signal type: PT1000

Set analogue input

Adjustment of type of use, signal type and corresponding signal/value assignment

Information about the current settings can be retrieved in “Overview of the analogue input”.

The type of use, signal type and signal/values assignment are defined in “Set analogue input”.

Settings dialogue setpoint sensor
Types of use

Type of use

Function

Not configured

This analogue input is not used. No settings required

Setpoint sensor

Use analogue input as setpoint sensor.

For example, delivery head.

Differential pressure sensor

Use analogue input as actual value input for differential pressure sensor.

For example, index circuit evaluator.

Temperature sensor

Use analogue input as actual value input for temperature sensor.

For example for control mode T-const

External sensor

Use analogue input as actual value input for PID control.

The following signal types are available depending on the type of use:

Signal types

Type of use

Signal type

Setpoint sensor

• 0 – 10 V, 2 – 10 V

• 0 to 20 mA, 4 to 20 mA

Differential pressure sensor

• 0 – 10 V, 2 – 10 V

• 0 to 20 mA, 4 to 20 mA

Temperature sensor

• PT1000

• 0 – 10 V, 2 – 10 V

• 0 to 20 mA, 4 to 20 mA

External sensor

• 0 – 10 V, 2 – 10 V

• 0 to 20 mA, 4 to 20 mA

Example setpoint sensor

The following signal types are available for the type of use “Setpoint sensor”:

Setpoint sensor signal types:

0 ... 10 V: voltage range of 0 ... 10 V for transfer of setpoints.

2 ... 10 V: voltage range of 2 ... 10 V for transfer of setpoints. Cable break is detected for a voltage below 2 V.

0 ... 20 mA: electric current range of 0 ... 20 mA for transfer of setpoints.

4 ... 20 mA: electric current range of 4 ... 20 mA for transfer of setpoints. Cable break is detected for a electric current below 4 mA.

NOTICE

notice

The substitute setpoint is adjusted in the event of cable break detection.

For the signal types “0 ... 10 V” and “0 ... 20 mA”, a cable break detection with a parameterisable threshold can be optionally activated (see setpoint sensor configuration).