Combined mode

Combined mode

The control input of the main pump and the control input of the partner pump are respectively occupied with a control cable and configured to EXT. OFF. The control input of the main pump switches both dual-pump partners off. The control input of the partner pump only switches the partner pump off. If the main pump malfunctions or if the twin-head pump connection is disconnected, the control input of the partner pump is assessed.

Combined mode

Main pump

Partner pump

States

EXT. OFF

Behaviour of the pump motor

Display text for active influences

EXT. OFF

Behaviour of the pump motor

Display text for active influences

1

Active

Off

OFF
Override OFF (DI1/2)

Active

Off

OFF
Override OFF (DI1/2)

2

Not active

On

OK; normal operation

Active

Off

OFF
Override OFF (DI1/2)

3

Active

Off

OFF
Override OFF (DI1/2)

Not active

Off

OFF
Override OFF (DI1/2)

4

Not active

On

OK; normal operation

Not active

On

OK; normal operation