Single pump mode
Single pump mode
The control input of the main pump and the control input of the partner pump are respectively occupied with a control cable and configured to EXT. OFF. Each of the two pumps is individually switched by its own control input. If the main pump malfunctions or if the twin-head pump connection is disconnected, the control input of the partner pump is assessed.
Alternatively, a cable jumper can also be put on the partner pump instead of a separate control cable.
Main pump | Partner pump | |||||
---|---|---|---|---|---|---|
States | EXT. OFF | Behaviour of the pump motor | Display text for active influences | EXT. OFF | Behaviour of the pump motor | Display text for active influences |
1 | Active | Off | OFF | Active | Off | OFF |
2 | Not active | On | OK; normal operation | Active | Off | OFF |
3 | Active | Off | OFF | Not active | On | OK; normal operation |
4 | Not active | On | OK; normal operation | Not active | On | OK; normal operation |