System mode

The control input of the main pump is occupied with a control cable and configured to EXT. OFF.
The control input on the main pump switches both dual-pump partners.
The control input of the partner pump is ignored and has no significance regardless of its configuration. If the main pump malfunctions or if the twin-head pump connection is disconnected, the partner pump is also stopped.

System mode

Main pump

Partner pump

States

EXT. OFF

Behaviour of the pump motor

Display text for active influences

EXT. OFF

Behaviour of the pump motor

Display text for active influences

1

Active

Off

OFF
Override OFF (DI1/2)

Active

Off

OFF
Override OFF (DI1/2)

2

Not active

On

OK; normal operation

Active

On

OK; normal operation

3

Active

Off

OFF
Override OFF (DI1/2)

Not active

Off

OFF
Override OFF (DI1/2)

4

Not active

On

OK; normal operation

Not active

On

OK; normal operation