Factory settings – defaults and parameters
Settings | Stratos MAXO (-D) | Stratos MAXO-Z |
---|---|---|
Set control mode | ||
Setting assistant | Radiator – Dynamic Adapt plus | Circulation – T-const. |
Pump On/Off | Motor on | Motor on |
Dual-pump operation | ||
Connect twin-head pump | Single pump: not connected Twin-head pump/two-pump system: connected | - - |
Twin-head pump alteration | 24 h | - |
Additional functions | ||
No-Flow Stop | not active | not active |
QLimit | not active | not active |
Night setback | not active | not active |
Bluetooth | active | active |
External interfaces | ||
SSM relay | ||
Function SSM relay | Fault(s) only | Fault(s) only |
Trigger delay | 5 s | 5 s |
Reset delay | 5 s | 5 s |
SBM relay | ||
Function SBM relay | Motor in operation | Motor in operation |
Trigger delay | 5 s | 5 s |
Reset delay | 5 s | 5 s |
DI1 | not configured | not configured |
DI2 | not configured | not configured |
AI1 | not configured | not configured |
AI2 | not configured | not configured |
Wilo Net | ||
Wilo Net termination | switched on (for twin-head pumps) | switched off |
Wilo Net address | Twin-head pump Main pump: ID 1 Single pump: ID 127 | ID 127 |
Device settings | ||
Language | English | English |
Units | m, m3/h | m, m3/h |
Pump kick | switched on | switched on |
Pump kick time interval | 24 h | 24 h |
Diagnostics and measured values | ||
Diagnostics help | ||
SSM forced control (normal, active, inactive) | inactive | inactive |
SBM forced control (normal, active, inactive) | inactive | inactive |
Heating/cooling quantity measurement | ||
Heat/cooling quantity On/Off | switched off | switched off |
Sensor feed temperature | not configured | not configured |
Return temperature sensor | not configured | not configured |
Maintenance | ||
Pump kick | switched on | switched on |
Pump kick time interval | 24 h | 24 h |
Basic function mode | Control mode | Control mode |
Ramp time | 0 s | 0 s |