Gradient ∆p-v characteristic curve
A factor can be set on the pump to optimise the Δp-v control characteristic.
The additional function “Slope of ∆p-v characteristic curve” can only be used for the differential pressure control Δp‑v.
The slope of the ∆p‑v characteristic curve is set via the Context button . The factor 50 % (½ Hset) is pre-set at the factory.
NOTICE
In some installations with special pipe network characteristics, there may be inadequate or excessive supply. The factor reduces (< 50 %) or increases (> 50 %) the Δp-v delivery head at Q=0 m³/h.
- Factor < 50 %: ∆p‑v characteristic curve becomes steeper.
- Factor > 50 %: ∆p‑v characteristic curve becomes flatter.
- Factor 100 % is equal to an Δp-c control.
The excessive or inadequate supply can be compensated by adjusting the factor.
- In case of inadequate supply in the partial load range, the value must be increased.
- In case of excessive supply in the partial load range, the value can be reduced. More energy can be saved and flow noises are reduced.
NOTICE