No-Flow Stop

The additional control function “No-Flow Stop” continuously monitors the actual volume flow of the heating/cooling system.
If the volume flow decreases due to closing valves and falls below the “No-Flow Stop Limit” threshold set for No-Flow Stop, the pump is stopped.
The pump checks every 5 minutes (300 s) whether the volume flow demand is increasing again. When the volume flow increases again, the pump continues running in its set control mode in normal operation.

NOTICE

notice

A volume flow increase relative to the set minimum volume flow “No-Flow Stop Limit” is checked within a time interval of 10 s.

NOTICE

notice

The test time of 5 minutes is permanently set and cannot be adjusted.

The reference volume flow Qref can be set between 1% and 20% of the maximum volume flow QMax depending on the pump size.

Field of application of No-Flow Stop:

A pump in a consumer circuit with control valves in heating or cooling (with radiators, fan heaters, air-conditioning devices, underfloor heating/cooling, ceiling heating/cooling, concrete core heating/cooling) as an additional function for all control modes except Multi-Flow Adaptation and volume flow Q-const.

NOTICE

notice

This function is deactivated in the factory settings and must be activated if required.

NOTICE

notice

The additional control function “No-Flow Stop” is an energy-saving function. Reducing unnecessary running times saves electrical pumping energy.

NOTICE

notice

The additional “No-Flow Stop” control function is available for suitable applications only! The additional control function “No-Flow Stop” cannot be combined with the additional control function “Q-LimitMin”!