Pre-defined applications in the setting assistant
The following applications can be selected via the setting assistant:
Pre-defined system types with control modes and optional additional control functions in the setting assistant
Heating application
System type/control mode | Night setback | No-Flow Stop | Q-LimitMax | Q-LimitMin | Multi-Flow Adaptation Mixer |
---|---|---|---|---|---|
Radiator | |||||
Differential pressure Δp-v | X | X | X | ||
Dynamic Adapt plus | X | ||||
Hall temperature T-const. | X | X | |||
Underfloor heating | |||||
Differential pressure Δp-c | X | X | X | ||
Dynamic Adapt plus | X | ||||
Hall temperature T-const. | X | X | |||
Ceiling heating | |||||
Differential pressure Δp-c | X | X | X | ||
Dynamic Adapt plus | X | ||||
Hall temperature T-const. | X | X | |||
Fan heater | |||||
Differential pressure Δp-v | X | X | X | ||
Dynamic Adapt plus | X | ||||
Hall temperature T-const. | X | X | |||
Concrete core heating | |||||
Differential pressure Δp-c | X | X | X | ||
Dynamic Adapt plus | X | ||||
Feed/return ΔT | X | X | X | ||
Volume flow Q-const. | X | ||||
Hydraulic shunt | |||||
Sec. feed temperature T-const. | X | X | |||
Return Δ-T | X | x | ● | ||
Multi-Flow Adaptation | X | X | |||
Volume flow Q-const. | X | ||||
Differential pressure-less distributor | |||||
Multi-Flow Adaptation | X | X | |||
Volume flow Q-const. | X | ||||
Buffer heating | |||||
Multi-Flow Adaptation | X | X | |||
Volume flow Q-const. | X | ||||
Heat exchanger | |||||
Sec. feed temperature T-const. | X | X | |||
Feed Δ-T | X | x | ● | ||
Multi-Flow Adaptation | X | X | |||
Volume flow Q-const. | X | ||||
Heat source circuit | |||||
Feed/return ΔT | X | X | X | ||
Volume flow Q-const. | X | ||||
District heating circuit | |||||
Differential pressure Δp-c | X | X | X | ||
Differential pressure Δp-v | X | X | X | ||
Index circuit Δp-c | X | X | X | ||
Basic control modes | |||||
Differential pressure Δp-c | X | X | X | X | |
Differential pressure Δp-v | X | X | X | X | |
Index circuit Δp-c | X | X | X | X | |
Dynamic Adapt plus | X | ||||
Volume flow Q-const. | X | ||||
Multi-Flow Adaptation | X | X | |||
Temperature T-const. | x | X | X | X | |
Temperature ΔT-const. | X | X | X | X | |
Speed n-const. | X | X | X | x | |
●: permanently activated additional control function |
Pre-defined system types with control modes and optional additional control functions in the setting assistant
Cooling application
System type/control mode | Night setback | No-Flow Stop | Q-LimitMax | Q-LimitMin | Multi-Flow Adaptation Mixer |
---|---|---|---|---|---|
Ceiling cooling | |||||
Differential pressure Δp-c | X | X | |||
Dynamic Adapt plus | |||||
Hall temperature T-const. | X | ||||
Underfloor cooling | |||||
Differential pressure Δp-c | X | X | |||
Dynamic Adapt plus | |||||
Hall temperature T-const. | X | ||||
Air-conditioning device | |||||
Differential pressure Δp-v | X | X | |||
Dynamic Adapt plus | X | ||||
Hall temperature T-const. | X | ||||
Concrete core cooling | |||||
Differential pressure Δp-c | X | X | |||
Dynamic Adapt plus | |||||
Feed/return ΔT | X | X | |||
Volume flow Q-const. | |||||
Hydraulic shunt | |||||
Sec. feed temperature T-const. | X | ||||
Return Δ-T | x | ● | |||
Multi-Flow Adaptation | X | X | |||
Volume flow Q-const. | |||||
Differential pressure-less distributor | |||||
Multi-Flow Adaptation | X | X | |||
Volume flow Q-const. | |||||
Buffer cooling | |||||
Multi-Flow Adaptation | X | X | |||
Volume flow Q-const. | |||||
Heat exchanger | |||||
Sec. feed temperature T-const. | X | ||||
Feed Δ-T | x | ● | |||
Multi-Flow Adaptation | X | X | |||
Volume flow Q-const. | |||||
Re-cooling circuit | |||||
Volume flow Q-const. | |||||
District cooling circuit | |||||
Differential pressure Δp-c | X | X | |||
Differential pressure Δp-v | X | X | |||
Index circuit Δp-c | X | X | |||
Basic control modes | |||||
Differential pressure Δp-c | X | X | X | ||
Differential pressure Δp-v | X | X | X | ||
Index circuit Δp-c | X | X | X | ||
Dynamic Adapt plus | |||||
Volume flow Q-const | |||||
Multi-Flow Adaptation | X | X | |||
Temperature T-const. | x | X | X | ||
Temperature ΔT-const. | X | X | X | ||
Speed n-const. | X | X | x | ||
●: permanently activated additional control function |
Pre-defined system types with control modes and optional additional control functions in the setting assistant
Drinking water application
System type/control mode | Night setback | No-Flow Stop | Q-LimitMax | Q-LimitMin | Detection of |
---|---|---|---|---|---|
Drinking water (circulation) | |||||
Temperature T-const. | x | X | X | ||
Drinking water storage tank | |||||
Charge pump | X | X | |||
Basic control modes | |||||
Differential pressure Δp-c | X | X | X | X | |
Differential pressure Δp-v | X | X | X | X | |
Index circuit Δp-c | X | X | X | X | |
Dynamic Adapt plus | X | ||||
Volume flow Q-const. | |||||
Multi-Flow Adaptation | X | ||||
Temperature T-const. | x | X | X | X | |
Temperature ΔT-const. | X | X | X | X | |
Speed n-const. | X | X | X | x | |
●: permanently activated additional control function |
NOTICE
The additional control functions No-Flow Stop und Q-LimitMin. cannot be active simultaneously.