Pre-defined applications in the setting assistant

The following applications can be selected via the setting assistant:

Pre-defined system types with control modes and optional additional control functions in the setting assistant

Heating application

Heating application

System type/control mode

Night setback

No-Flow Stop

Q-LimitMax

Q-LimitMin

Multi-Flow Adaptation

Mixer

Radiator

Differential pressure Δp-v

X

X

X

Dynamic Adapt plus

X

Hall temperature T-const.

X

X

Underfloor heating

Differential pressure Δp-c

X

X

X

Dynamic Adapt plus

X

Hall temperature T-const.

X

X

Ceiling heating

Differential pressure Δp-c

X

X

X

Dynamic Adapt plus

X

Hall temperature T-const.

X

X

Fan heater

Differential pressure Δp-v

X

X

X

Dynamic Adapt plus

X

Hall temperature T-const.

X

X

Concrete core heating

Differential pressure Δp-c

X

X

X

Dynamic Adapt plus

X

Feed/return ΔT

X

X

X

Volume flow Q-const.

X

Hydraulic shunt

Sec. feed temperature T-const.

X

X

Return Δ-T

X

x

Multi-Flow Adaptation

X

X

Volume flow Q-const.

X

Differential pressure-less distributor

Multi-Flow Adaptation

X

X

Volume flow Q-const.

X

Buffer heating

Multi-Flow Adaptation

X

X

Volume flow Q-const.

X

Heat exchanger

Sec. feed temperature T-const.

X

X

Feed Δ-T

X

x

Multi-Flow Adaptation

X

X

Volume flow Q-const.

X

Heat source circuit
heat pump

Feed/return ΔT

X

X

X

Volume flow Q-const.

X

District heating circuit

Differential pressure Δp-c

X

X

X

Differential pressure Δp-v

X

X

X

Index circuit Δp-c

X

X

X

Basic control modes

Differential pressure Δp-c

X

X

X

X

Differential pressure Δp-v

X

X

X

X

Index circuit Δp-c

X

X

X

X

Dynamic Adapt plus

X

Volume flow Q-const.

X

Multi-Flow Adaptation

X

X

Temperature T-const.

x

X

X

X

Temperature ΔT-const.

X

X

X

X

Speed n-const.

X

X

X

x

●: permanently activated additional control function
x: available additional control function for the control mode

Pre-defined system types with control modes and optional additional control functions in the setting assistant

Cooling application

Cooling application

System type/control mode

Night setback

No-Flow Stop

Q-LimitMax

Q-LimitMin

Multi-Flow Adaptation

Mixer

Ceiling cooling

Differential pressure Δp-c

X

X

Dynamic Adapt plus

Hall temperature T-const.

X

Underfloor cooling

Differential pressure Δp-c

X

X

Dynamic Adapt plus

Hall temperature T-const.

X

Air-conditioning device

Differential pressure Δp-v

X

X

Dynamic Adapt plus

X

Hall temperature T-const.

X

Concrete core cooling

Differential pressure Δp-c

X

X

Dynamic Adapt plus

Feed/return ΔT

X

X

Volume flow Q-const.

Hydraulic shunt

Sec. feed temperature T-const.

X

Return Δ-T

x

Multi-Flow Adaptation

X

X

Volume flow Q-const.

Differential pressure-less distributor

Multi-Flow Adaptation

X

X

Volume flow Q-const.

Buffer cooling

Multi-Flow Adaptation

X

X

Volume flow Q-const.

Heat exchanger

Sec. feed temperature T-const.

X

Feed Δ-T

x

Multi-Flow Adaptation

X

X

Volume flow Q-const.

Re-cooling circuit

Volume flow Q-const.

District cooling circuit

Differential pressure Δp-c

X

X

Differential pressure Δp-v

X

X

Index circuit Δp-c

X

X

Basic control modes

Differential pressure Δp-c

X

X

X

Differential pressure Δp-v

X

X

X

Index circuit Δp-c

X

X

X

Dynamic Adapt plus

Volume flow Q-const

Multi-Flow Adaptation

X

X

Temperature T-const.

x

X

X

Temperature ΔT-const.

X

X

X

Speed n-const.

X

X

x

●: permanently activated additional control function
x: available additional control function for the control mode

Pre-defined system types with control modes and optional additional control functions in the setting assistant

Drinking water application

Drinking water application

System type/control mode

Night setback

No-Flow Stop

Q-LimitMax

Q-LimitMin

Detection of
disinfection

Drinking water (circulation)

Temperature T-const.

x

X

X

Drinking water storage tank

Charge pump

X

X

Basic control modes

Differential pressure Δp-c

X

X

X

X

Differential pressure Δp-v

X

X

X

X

Index circuit Δp-c

X

X

X

X

Dynamic Adapt plus

X

Volume flow Q-const.

Multi-Flow Adaptation

X

Temperature T-const.

x

X

X

X

Temperature ΔT-const.

X

X

X

X

Speed n-const.

X

X

X

x

●: permanently activated additional control function
x: available additional control function for the control mode

NOTICE