Level sensor
1 | Retaining pipe |
2 | Level sensor |
- To prevent backflow in the inlet pipe, set the switching point “Pump ON” approx. 50 mm (2.5 in) below the inlet floor.
- Lower part of the level sensor is permanently immersed.
- Insert the level sensor into the retaining pipe.
- Adjust the switching points in the switchgear.
DrainLift | Pump ON* | Pump OFF | High water alarm* |
---|---|---|---|
WS 40 ... | 0.4 m (16 in) | 0.2 m (8 in) | 0.45 m (18 in) |
WS 50 ... | 0.4 m (16 in) | 0.2 m (8 in) | 0.45 m (18 in) |
* The values refer to an inlet floor of 450 mm (17.5 in). The value can be adjusted if the inlet is higher.