Installation – ground installation (under ground)

DANGER

danger

Danger due to fluids hazardous to health during installation!

Danger of bacterial infection!

  1. Clean and disinfect installation location.
  2. Wipe up drips immediately.
  3. Observe the specifications of the factory regulations!
  4. If contact with fluids that are hazardous to health is possible, wear the following protective equipment:
  5. sealed safety glasses
  6. mouth protection
  7. safety gloves

DANGER

danger

Risk of fatal injury due to dangerous lone working practices!

Work in chambers and narrow rooms as well as work involving risk of falling are dangerous work. Such work may not be carried out autonomously!

  1. Only carry out work with another person!

WARNING

warning

Suspended loads!

Danger of (serious) injuries caused by falling parts.

  1. Standing under suspended loads is prohibited!
  2. Do not move loads over workplaces where persons are present!

CAUTION

Buoyancy due to high ground water level!

Elevated groundwater can cause the pump chamber to float up.

  1. Observe information on the maximum permissible groundwater level.

CAUTION

Malfunction due to frost!

Frost can cause malfunctions and damage.

  1. Pay attention to local frost depths.
  2. If the unit or discharge outlet are in the freezing zone, take the unit out of operation during freezing periods.

NOTICE

notice

Installation of the pump chamber outside buildings

Observe EN 1610 and local regulations during ground installation!