Soft starter
- Full load
- Set the motor protection to the rated current according to the rating plate.
- Partial load operation
- Set the motor protection to 5 % above the current measured at the duty point.
Please observe the following points:
- Current consumption must always be below the rated current.
- Complete starting and stopping within 30 s.
- To avoid power dissipation, bypass the electronic starter (soft start) once normal operation is reached.