Shut-down
The mixer is deactivated but remains installed. This ensures that the mixer is always ready for operation.
- To protect the mixer from frost, ice and direct sunlight, immerse the mixer completely in the fluid.
- Minimum fluid temperature: +3 °C (+37 °F).
- Switch off the mixer.
- Secure the operating point against being switched on again by unauthorised persons (e.g. lock main switch).
- The mixer has been decommissioned and can be dismantled.
If the mixer remains installed after decommissioning, observe the following:
- Ensure that the aforementioned requirements are maintained for the complete period of shutdown. If these requirements cannot be guaranteed, remove the mixer.
- For an extended period of shutdown, carry out a function test at regular intervals:
- Period: monthly to quarterly
- Running time: 5 minutes
- Only run a function test in valid operating conditions!