Pre-defined applications in the settings assistant

The following applications can be selected via the settings assistant:

Pre-defined applications in the settings assistant

Pre-defined applications in the settings assistant

Available additional control functions

Radiator – Differential pressure Δp-v

For the “Heating with radiators” application, there is an optimized variable differential pressure control. Consumer loads with connected radiators can be supplied with a variable differential pressure control (Δp-v) according to the needs.
Assuming a maximum required delivery head at the design point, the pump variably adjusts the differential pressure to the volume flow. The volume flow varies through the open and closed valves at the consumers. The pump output is adjusted to the requirements of the consumer load and the energy requirement is significantly reduced.

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max

Radiator – Dynamic Adapt plus

For the “Heating with radiators” application, a control function is available with Dynamic Adapt plus, which automatically and continuously adjusts the required pump output based on the requirements of the heating system.
Dynamic Adapt plus does not require setpoint adjustments, the control is executed automatically without the availability of the design point. The pump continuously adjusts its delivery rate to the requirements of the consumer loads and to the status of the open and closed valves and thus reduces energy requirements significantly.

‣ Setback operation

Radiator – Hall temperature T-const

For applications, in which the pump supplies only one room/hall with radiators, there is a temperature control, which not only adjusts the pump output to the temperature requirements of a room/hall, but also controls the temperature of the room/hall. This control mode does not require hydraulic control valves and prevents hydraulic loss.
In order to control the hall temperature, the pump requires a temperature sensor, which records the current temperature of the room. For this purpose, commercially available temperature sensors such as PT1000 sensors can be connected to an analogue input of the pump.

‣ Setback operation
‣ Q-Limit Max

Underfloor heating – Differential pressure Δp-c

For the “Heating with underfloor heating” application, there is an optimized constant differential pressure control. Consumer loads with underfloor heating can be supplied with a constant differential pressure control (dp-c) according to the needs.
Assuming a maximum required delivery head at the design point, the pump variably adjusts the pump output to the required volume flow. The volume flow varies through the open and closed valves at the heating circuits. The pump output is adjusted to the requirements of the consumer load and the energy requirement is reduced.

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max

 

Underfloor heating – Dynamic Adapt plus

For the “Heating with underfloor heating” application, Dynamic Adapt plus provides a control function that automatically and continuously adjusts the required pump output based on the requirements of the heating system.
Dynamic Adapt plus does not require setpoint adjustments, the control mode does not require the design point. The pump continuously adjusts its delivery rate to the requirements of the consumer loads and to the status of the open and closed valves and thus reduces energy requirements significantly.

‣ Setback operation

Underfloor heating – Hall temperature T-const

For applications, in which the pump supplies only one room/hall with underfloor heating, there is a temperature control, which not only adjusts the pump output to the temperature requirements of a room/hall, but also controls the temperature of the room/hall. This control mode does not require hydraulic control valves and prevents hydraulic loss.
In order to control the hall temperature, the pump requires a temperature sensor, which records the current temperature of the room. For this purpose, commercially available temperature sensors such as PT1000 sensors can be connected to an analogue input of the pump.

‣ Setback operation
‣ Q-Limit Max

Ceiling heating – Differential pressure Δp-c

For the “Heating with ceiling heating” application, there is an optimized constant differential pressure control. Consumer loads with ceiling heating can be supplied with a constant differential pressure control (Δp-c) according to the needs.
Assuming a maximum required delivery head at the design point, the pump variably adjusts the pump output to the required volume flow. The volume flow varies through the open and closed valves at the heating circuits. The pump output is adjusted to the requirements of the consumer load and the energy requirement is reduced.

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max

Ceiling heating – Dynamic Adapt plus

For the “Heating with ceiling heating” application, Dynamic Adapt plus provides a control function that automatically and continuously adjusts the required pump output based on the requirements of the heating system.
Dynamic Adapt plus does not require setpoint adjustments, the control mode does not require the design point. The pump continuously adjusts its delivery rate to the requirements of the consumer loads and to the status of the open and closed valves and thus reduces energy requirements significantly.

‣ Setback operation

Ceiling heating – Hall temperature T-const

For applications, in which the pump supplies only one room/hall with ceiling heating, there is a temperature control, which not only adjusts the pump output to the temperature requirements of a room/hall, but also controls the temperature of the room/hall. This control mode does not require hydraulic control valves and prevents hydraulic loss.
In order to control the hall temperature, the pump requires a temperature sensor, which records the current temperature of the room. For this purpose, commercially available temperature sensors such as PT1000 sensors can be connected to an analogue input of the pump.

‣ Setback operation
‣ Q-Limit Max

Fan heater – Differential pressure Δp-v

For the “Heating with fan heater” application, there is an optimized variable differential pressure control. Consumer loads with connected fan heaters can be supplied with a variable differential pressure control (Δp-v) according to the needs.
Assuming a maximum required delivery head at the design point, the pump variably adjusts the differential pressure to the volume flow. The volume flow varies through the open and closed valves at the consumers. The pump output is adjusted to the requirements of the consumer load and the energy requirement is significantly reduced.

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max

Fan heater – Dynamic Adapt plus

‣ Setback operation

Fan heater – Hall temperature T-const

‣ Setback operation
‣ Q-Limit Max

 

Hydraulic shunt – Feed temperature T-const

‣ Q-Limit Max

Hydraulic shunt – Return ΔT

‣ Q-Limit Max

• Fixed activation addition control function:

‣ Q-Limit Min

Hydraulic shunt – Multi-Flow Adaptation

‣ Q-Limit Min

Heat exchanger – Feed temperature T-const

‣ Q-Limit Max

Heat exchanger – Feed ΔT

‣ Q-Limit Max

• Fixed activation addition control function:

‣ Q-Limit Min

Heat exchanger – Multi-Flow Adaptation

‣ Q-Limit Min

Heating – Differential pressure Δp-c

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Heating – Differential pressure Δp-v

For the “Heating” application, there is an optimized variable differential pressure control. Consumer loads with connected consumers can be supplied with a variable differential pressure control (Δp-v) according to the needs.
Assuming a maximum required delivery head at the design point, the pump variably adjusts the differential pressure to the volume flow. The volume flow varies through the open and closed valves at the consumers. The pump output is adjusted to the requirements of the consumer load and the energy requirement is significantly reduced.

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Heating – Index circuit Δp-c

For the “Heating with index circuit Δp-c” application, there is an optimized constant differential pressure control. This differential pressure control ensures supply in a poorly compensated heating system.
The pump takes into account the point in the heating system which is the most difficult to supply.
For this purpose, the pump requires a differential pressure sensor which is installed at this point in the system.
The delivery head must be adjusted to the required differential pressure at this point and the pump output is adjusted according to the requirements of the consumer loads there.

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Heating – Dynamic Adapt plus

‣ Setback operation

Heating – Volume flow Q-const

‣ Setback operation

Heating – Multi-Flow Adaptation

‣ Q-Limit Min

Heating – Temperature T-const

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Heating – Temperature ΔT-const

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Heating – Speed n-const

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Ceiling cooling – Differential pressure Δp-c

‣ No-Flow Stop
‣ Q-Limit Max

Ceiling cooling – Dynamic Adapt plus

No additional control functions

Ceiling cooling – Hall temperature T-const

‣ Q-Limit Max

Underfloor cooling – Differential pressure Δp-c

‣ No-Flow Stop
‣ Q-Limit Max

Underfloor cooling – Dynamic Adapt plus

No additional control functions

Underfloor cooling – Hall temperature T-const

‣ Q-Limit Max

Air-conditioning device – Differential pressure Δp-v

‣ No-Flow Stop
‣ Q-Limit Max

Air-conditioning device – Dynamic Adapt plus

‣ Setback operation

Air-conditioning device – Hall temperature T-const

‣ Q-Limit Max

Hydraulic shunt – Feed temperature T-const

‣ Q-Limit Max

Hydraulic shunt – Return ΔT

‣ Q-Limit Max

• Fixed activation addition control function:

‣ Q-Limit Min

Hydraulic shunt – Multi-Flow Adaptation

‣ Q-Limit Min

Heat exchanger – Feed temperature T-const

‣ Q-Limit Max

Heat exchanger – Feed ΔT

‣ Q-Limit Max

• Fixed activation addition control function:

‣ Q-Limit Min

Heat exchanger – Multi-Flow Adaptation

‣ Q-Limit Min

Cooling – Differential pressure Δp-c

‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Cooling – Differential pressure Δp-v

‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Cooling – Index circuit Δp-c

For the “Cooling with index circuit Δp-c” application, there is an optimized constant differential pressure control. This differential pressure control ensures supply in a poorly compensated cooling system.
The pump takes into account the point in the cooling system which is the most difficult to supply.
For this purpose, the pump requires a differential pressure sensor, which is installed at this point in the system.
The delivery head must be adjusted to the required differential pressure at this point and the pump output is accordingly adjusted to the requirements of the consumer loads there.

‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Cooling – Dynamic Adapt plus

No additional control functions

Cooling – volume flow Q-const

No additional control functions

Cooling – Multi-Flow Adaptation

‣ Q-Limit Min

Cooling – Temperature T-const

‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Cooling – Temperature ΔT-const

‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Cooling – Speed n-const

‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Drinking water – Temperature T-const

Detection of disinfection:

The “Detection of disinfection” function has been provided in the “Set auto control” menu after having selected the “Drinking water – temperature T-const” application in the settings assistant.
This function monitors the feed temperature at the hot water source with an external temperature sensor in order to record the significant increase of temperature in case of thermal disinfection.
Once the system detects thermal disinfection, the pump switches to maximum output to support disinfection and rinse the system with hot water.

NOTICE: If the “Detection of disinfection” option is not used, the pump reduces the power when it detects a temperature increase. This prevents thermal disinfection.
Ensure the system is rinsed with hot fluid on the basis of other measures:

• Manual selection of “MAX” function in the “Settings” “Manual operation” menu.

• External control of the “External MAX” function through a binary input.

‣ Detection of disinfection
‣ Q-Limit Max
‣ Q-Limit Min

Drinking water accumulator – Charge pump ΔT

‣ Q-Limit Max

• Fixed activation addition control function:

‣ Q-Limit Min

Drinking water accumulator – Accumulator charging temperature

‣ Q-Limit Max

• Fixed activation addition control function:

‣ Q-Limit Min

Drinking water accumulator – Multi-Flow Adaptation

No additional control functions

Drinking water – Differential pressure Δp-c

‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Drinking water – Differential pressure Δp-v

‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Drinking water – Index circuit Δp-c

‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Drinking water – Volume flow Q-const

No additional control functions

Drinking water – Multi-Flow Adaptation

‣ Q-Limit Min

Drinking water – Temperature T-const

‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Drinking water – Temperature ΔT-const

‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Drinking water – Speed n-const

‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Differential pressure Δp-c

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Differential pressure Δp-v

A variable differential pressure control is available for the application. Consumer loads with connected consumers can be supplied with a variable differential pressure control (Δp-v) according to the needs.
Assuming a maximum required delivery head at the design point, the pump variably adjusts the differential pressure to the volume flow. The volume flow varies through the open and closed valves at the consumers. The pump output is adjusted to the requirements of the consumer load and the energy requirement is significantly reduced.

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Index circuit Δp-c

A constant differential pressure control is available for the “Index circuit Δp-c” application. This differential pressure control ensures supply in a poorly compensated hydraulic system.
The pump takes into account the point in the hydraulic system which is the most difficult to supply.
For this purpose, the pump requires a differential pressure sensor which is installed at this point in the system.
The delivery head must be adjusted to the required differential pressure at this point and the pump output is accordingly adjusted to the requirements of the consumer loads there.

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Dynamic Adapt plus

‣ Setback operation

Volume flow Q-const

‣ Setback operation
‣ No-Flow Stop

Multi-Flow Adaptation

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Temperature T-const

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Temperature ΔT-const

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

Speed n-const

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min

PID control

‣ Setback operation
‣ No-Flow Stop
‣ Q-Limit Max
‣ Q-Limit Min