Warning messages
Warning displayed:
- The status display is marked in yellow.
- Warning message, warning code (W...), cause and remedy are described as text.
Display of a warning in 7-segment LED display:
- The warning is displayed with a red coloured warning code (H…).

Warnings indicate restricted pump function. The pump continues to operate in restricted mode (emergency operation).
Depending on the cause of the warning, emergency operation leads to a restriction of the control function and even reactivation of a fixed speed.
If the pump identifies as part of permanent monitoring that the cause of the warning no longer applies, the warning is revoked and operation resumes.
If a warning message is output, the display is permanently on and the green LED indicator is off.
Code | Fault | Cause | Remedy |
---|---|---|---|
550 | There is flow through the pump in the opposite direction of flow. | External influences cause flow against the direction of the pump’s flow. | Check power control of the pumps, |
Additional information about causes and remedy: | |||
551 | Undervoltage | Power supply has dropped below 195 V. | Check power supply. |
Additional information about causes and remedy: | |||
552 | There is externally generated flow through the pump in the direction of flow. | External influences cause flow in the pump’s direction of flow. | Check power control of the other pumps. |
Additional information about causes and remedy: | |||
553 | Control module faulty. | Control module faulty. | Replace the control module. |
Additional information about causes and remedy | |||
554 | MFA1) pump is not reachable. | A MFA1) partner pump no longer reacts to requests. | Check Wilo Net connection or power supply of the partner pump. |
Additional information about causes and remedy | |||
555 | No plausible sensor value at analogue input AI 1. | The configuration and the present signal lead to an unusable sensor value. | Check configuration of the input and connected sensor. |
Additional information about causes and remedy | |||
556 | Cable break at analogue input AI 1. | The configuration and the present signal help identify the cable break. | Check configuration of the input and connected sensor. |
Additional information about causes and remedy: | |||
557 | No plausible sensor value at analogue input AI 2. | The configuration and the present signal lead to an unusable sensor value. | Check configuration of the input and connected sensor. |
Additional information about causes and remedy | |||
558 | Cable break at analogue input AI 2. | The configuration and the present signal help identify the cable break. | Check configuration of the input and connected sensor. |
Additional information about causes and remedy: | |||
559 | Control module too hot. | Permissible temperature of the control module exceeded. | Ensure permissible ambient temperature. Improve room ventilation. |
Additional information about causes and remedy: | |||
560 | Incomplete software update. | The software update was not completed. | Software update with new software bundle is recommended. |
Additional information about causes and remedy: | |||
561 | Voltage analogue input overloaded (binary). | Voltage analogue input short-circuited or too heavily loaded. | Check line and consumers connected to power supply of analogue input for short-circuit. |
Additional information about causes and remedy: | |||
562 | Voltage analogue input overloaded (analogue). | Voltage analogue input short-circuited or too heavily loaded. | Check line and consumers connected to power supply of analogue input for short-circuit. |
Additional information about causes and remedy: | |||
563 | Sensor value missing from BMS. | Sensor source or BMS is configured incorrectly. | Check configuration and function of BMS. |
Additional information about causes and remedy: | |||
564 | Setpoint missing from BMS. | Sensor source or BMS is configured incorrectly. | Check configuration and function of BMS. |
Additional information about causes and remedy: | |||
565 | Signal too strong to analogue input AI 1. | The available signal is significantly over the expected maximum. | Check input signal. |
Additional information about causes and remedy: | |||
566 | Signal too strong to analogue input AI 2. | The available signal is significantly over the expected maximum. | Check input signal. |
Additional information about causes and remedy: | |||
567 | Calibration of Wilo sensor missing. | Concurrent replacement of control module and sensor with spare parts. | Replacement of a component, short commissioning |
Additional information about causes and remedy: | |||
568 | Wilo sensor cannot operate. | Wilo sensor cannot detect fluid. | Check fluid availability. |
Additional information about causes and remedy: | |||
569 | Configuration missing. | Pump configuration is missing. | Configure pump. Software update is recommended. |
Additional information about causes and remedy: | |||
570 | Control module too hot. | Permissible temperature of the control module exceeded. | Ensure permissible ambient temperature. Improve room ventilation. |
Additional information about causes and remedy: | |||
571 | Double pump connection interrupted. | The connection to the double pump partner cannot be made. | Check power supply of the double pump partner, cable connection and configuration. |
Additional information about causes and remedy: | |||
572 | Dry run detected. | The pump has detected power consumption that is too low. | Check water pressure, valves and non-return valves. |
Additional information about causes and remedy: | |||
573 | Communication to HMI interrupted. | Internal communication to display and operating unit interrupted. | Check/clean contacts at the edge of the terminal room as well as the display and operating unit. |
Additional information about causes and remedy: | |||
574 | Communication to CIF module interrupted. | Internal communication to the CIF module interrupted. | Check/clean contacts between CIF module and control module. |
Additional information about causes and remedy: | |||
575 | Remote control not possible by radio. | The Bluetooth radio module is faulty. | Software update is recommended. |
Additional information about causes and remedy: | |||
576 | Communication with Wilo sensor interrupted. | Internal communication with Wilo sensor interrupted. | Check sensor cable, sensor socket and Wilo-Connector. |
Additional information about causes and remedy: | |||
577 | Software update cancelled. | The software update was not completed. | Software update with new software bundle is recommended. |
Additional information about causes and remedy: | |||
578 | HMI faulty. | A fault in the display and operating unit has been identified. | Replace display and operating unit. |
Additional information about causes and remedy: | |||
579 | HMI software not compatible. | Display and operating unit cannot communicate correctly with the pump. | Software update is recommended. |
Additional information about causes and remedy: | |||
580 | Too many wrong PIN entries. | Too many connection attempts with wrong PIN. | Disconnect power supply from the pump and switch it on again. |
Additional information about causes and remedy: | |||
581 | Double pump does not fit. | The double pump partner does not fit this type of pump. | Select/install appropriate double pump partner. |
Additional information about causes and remedy: | |||
582 | Double pump is not compatible. | Double pump partner is not compatible with this pump. | Select/install appropriate double pump partner. |
Additional information about causes and remedy: | |||
583 | Fluid temperature too high. | Fluid temperature is hotter than 110 °C. | Reduce fluid temperature. |
Additional information about causes and remedy: | |||
590 | MFA1) partner type is not appropriate. | A MFA1) partner does not the appropriate type. | Check type and software of the partner pump. |
Additional information about causes and remedy: |
1) MFA= Multi-Flow Adaptation