Application and function of analogue inputs AI1 and AI2

Analogue inputs can be used for setpoint input or actual value input. The allocation of setpoint and actual value specifications are freely configurable.

“Analogue input (AI 1) function” and “Analogue input (AI 2) function” are used to set the type of use (setpoint sensor, differential pressure sensor, external sensor, …), the signal type (0 – 10 V, 0 – 20 mA, …) and the corresponding signal/value assignments. In addition, information about the current settings can be queried.

In the “Settings” menu, select

  1. “External interfaces”
  2. External interfaces
  3. “Analogue input (AI 1) function” or “Analogue input (AI 2) function”.
Function analogue input

 

After selecting one of the options “Analogue input (AI1) function” or “Analogue input (AI2) function”, select the following query or setting:

Setting analogue input AI 1 or AI 2

Setting

Function control input AI 1 or AI 2

Overview of the analogue input

Overview of settings of this analogue input, for example:

• Type of use: Temperature sensor

• Signal type: PT1000

Set analogue input

Adjustment of type of use, signal type and corresponding signal/value assignment

Information about the current settings can be retrieved in “Overview of the analogue input”.

The type of use, signal type and signal/values assignment are defined in “Set analogue input”.

Settings dialogue setpoint sensor
Types of use

Type of use

Function

Not configured

Analogue input not used. Additional settings are not possible.

Setpoint controller

Use analogue input as setpoint sensor.

For example, delivery head.

Differential pressure sensor

Use analogue input as actual value input for differential pressure sensor.

For example, index circuit evaluator.

Temperature sensor

Use analogue input as actual value input for temperature sensor.

For example for control mode T-const

External sensor

Use analogue input as actual value input for PID control.

The following signal types are available depending on the type of use:

Signal types

Type of use

Signal type

Setpoint controller

• 0 – 10 V

• 2 – 10 V

• 0 – 20 mA

• 4 – 20 mA

Differential pressure sensor

• 0 – 10 V

• 2 – 10 V

• 0 – 20 mA

• 4 – 20 mA

Temperature sensor

• PT1000

• 0 – 10 V

• 2 – 10 V

• 0 – 20 mA

• 4 – 20 mA

External sensor

• 0 – 10 V

• 2 – 10 V

• 0 – 20 mA

• 4 – 20 mA

Example setpoint sensor

The following signal types are available for the type of use “Setpoint controller”:

Setpoint sensor signal types:

0 – 10 V: Voltage range of 0 – 10 V for transfer of setpoint values.

2 – 10 V: Voltage range of 2 – 10 V for transfer of setpoint values. Cable break is detected for a voltage below 2 V.

0 – 20 mA: Electric current range of 0 – 20 mA for transfer of setpoints.

4 – 20 mA: Electric current range of 4 – 20 mA for transfer of setpoints. Cable break is detected for a electric current below 4 mA.

NOTICE

The substitute setpoint is adjusted in the event of cable break detection.

For the signal types “0 – 10 V” and “0 – 20 mA”, a cable break detection with a parameterisable threshold can be optionally activated (see “Setpoint controller configuration”).

Setpoint sensor configuration

NOTICE

When an external signal is used at the analogue input as setpoint source, the setpoint value must be paired to the analogue signal.
Open the editor’s context menu for the affected setpoint for pairing.

The use of an external signal at the analogue input as setpoint source requires pairing of the setpoint value to the analogue signal:

In the “Settings” menu, select

  1. “Set auto control”.
  2. Depending on the selected control mode, the setpoint editor displays the adjusted setpoint (setpoint delivery head Δp-v, setpoint temperature T-c,…).
  3. Setpoint editor
  4. Select setpoint and confirm by pressing the operating button.
  5. Press context button and select “Setpoint of external source:”.

Selection of possible setpoint sources:

Setpoint source

 

NOTICE

When an analogue input is selected as setpoint source, but the type of use for example has been selected as “Not configured” or as actual value input, the pump displays a configuration warning.

The deviation type is accepted as setpoint.

Either another source must be selected or the source must be configured as setpoint source.

 

NOTICE

After selecting one of the external sources, the setpoint is paired to this external source and can no longer be adjusted in the setpoint editor or on the Home screen.
This pairing can exclusively be cancelled in the context menu of the setpoint editor (as described above) or in the “External setpoint source” menu. The setpoint source must be adjusted again to “Internal setpoint”.

The pairing between external source and setpoint is marked both in Home screen, and in the setpoint editor in blue. The status LED also becomes blue.

 

After selecting one of the external sources, the “External setpoint source” becomes available to configure the parameters of the external source.
For this purpose, go to the “Settings” menu and select

  1. “Set auto control”
  2. “External setpoint source”.
External setpoint source

Possible selection:

Set input for external setpoint

Set input for external setpoint

Select setpoint source

Set setpoint source

Substitute setpoint in the event of a cable break

The setpoint source can be changed in select “Setpoint source”.

Setpoint source

The setpoint source should be configured when an analogue input is used as source. To do this, select “Set setpoint source”.

Set input for external setpoint

Set input for external setpoint

Select setpoint source

Set setpoint source

Substitute setpoint in the event of a cable break

Possible selection of type of use to be adjusted:

Settings dialogue

Select “Setpoint controller” as setpoint source.

NOTICE

If another usage type has been set to “Not configured” in the “Select type of use” menu, check whether the analogue input is already used for another type of use.
If necessary, select a different source.

Select the “Signal type” after selecting the type of use:

Signal type

After selecting the signal type, it is defined how standard values are used:

Use standard values

Defined standards for the transfer of the signal are used with “Use specifications”. Finally the setting of the analogue input is ended as setpoint sensor.

Standard signal assignment

OFF:

1.0 V

ON:

2.0

Min:

3.0 V

Max:

10.0 V

Select “User-defined settings” to configure additional settings:
Optional cable break detection is available for 0 – 10 V and 0 – 20 mA signal types only.

Optional cable break detection

Select “Switched off” to switch off cable break detection.
Select “Switched on” to activate cable break detection only within an adjustable limit value.

Cable break limit value

Define limit value for cable break by turning the operating button and confirm by pressing it.

In the next step define whether

  • the analogue signal only changes the setpoint
  • and the pump is additionally switched off through the analogue signal.

A setpoint change can be done through analogue signals without switching on and off the pump through the signals. In this case, “Switched off” is selected.
If the “On/off by analogue signal” function is switched on, the limit values must be defined for the switch on/off.
Subsequently assign the MIN signal/value and MAX signal/value.

ON/OFF through analogue signal
Limit values for ON/OFF control through analogue signal

For the transfer of analogue signal values to setpoints, only the transfer ramp is now defined. For this purpose, the minimum and maximum support points of the characteristic curve are specified and the respective setpoints are amended (MIN signal/value assignment and MAX signal/value assignment).

Minimum signal/value assignment
Max. signal/value assignment

When all signal/value assignments have been performed, the setting of the analogue setpoint source is completed.

An editor for adjusting the substitute setpoint in the event of a cable break or wrong configuration of the analogue input will open.

Substitute setpoint in the event of a cable break

Select substitute setpoint. This setpoint is used when detecting a cable break at the external setpoint source.

 

Actual value sensor

The actual value sensor provides:

  • Temperature sensor values for temperature-dependent control modes:
    • Constant temperature
    • Differential temperature
    • Room temperature
  • Temperature sensors values for temperature-dependent additional functions:
    • Heating/cooling quantity measurement
    • Automatic heating/cooling switchover
    • Automatic detection of thermal disinfection
  • Differential pressure sensor values for:
    • Differential pressure control with index circuit actual value logging
  • User-defined sensor values for:
    • PID control

 

Possible signal types when selecting the analogue input as actual value input:

Actual value sensor signal types:

0 – 10 V: Voltage range of 0 – 10 V for transfer of measurement values.

2 – 10 V: Voltage range of 2 – 10 V for the transfer of measurement values. Cable break is detected for a voltage below 2 V.

0 – 20 mA: Electric current of 0 – 20 mA for transfer of measured values.

4 – 20 mA: Electric current range of 4 – 20 mA for transfer of measured values. A cable break is detected in case of electric current below 4 mA.

PT1000: The analogue input evaluates a PT1000 temperature sensor.

 

Actual value sensor configuration

NOTICE

The selection of the analogue input as a connection for a sensor requires the corresponding configuration of the analogue input.

First open the overview menu to view the current configuration and use of analogue input.

To do this, in the “Settings” menu, select

  1. “External interfaces”
  2. “Analogue input (AI1) function” or “Analogue input (AI2) function”
  3. “Overview of the analogue input”.

Type of use, signal type and other set values for selected analogue input will be displayed. In order to make or change settings:

In the “Settings” menu, select

  1. “External interfaces”
  2. “Analogue input (AI1) function” or “Analogue input (AI2) function”
  3. “Set analogue input”.

First select type of use:

Settings dialogue actual value sensor

Select one of the types of use “Differential pressure sensor”, “Temperature sensor” or “External sensor” as one of the usage types.

NOTICE

If another usage type has been set to “Not configured” in the “Select type of use” menu, check whether the analogue input is already used for another type of use.
If necessary, select a different source.

Select the “Signal type” after selecting the actual value sensor:

Signal type

When selecting the signal type “PT1000”, all settings for the sensor input are completed and all other signal types require additional settings.

For the transfer of analogue signal values to actual values, only the transfer ramp is now defined. For this purpose, the minimum and maximum support point of the characteristic curve is specified and the respective actual values are amended (MIN signal/value assignment and MAX signal/value assignment).

Minimum signal/value assignment, actual value sensor
Max signal/value assignment, actual value sensor

Data input is complete, once the minimum and maximum characteristic curve interpolation points have been entered.

 

NOTICE

If the signal type PT1000 was selected, it is possible to set a temperature correction value for the measured temperature. With this the electrical resistance of a long sensor cable can be compensated.

In the “Settings” menu, select

  1. “External interfaces”
  2. “Analogue input (AI1) function” or “Analogue input (AI2) function”
  3. “Temperature correction” and set correction value (offset).

 

NOTICE

Optionally specify the position of the sensor for better understanding of the connected sensor’s function.
This configured position does not influence the function or sensor use.

In the “Settings” menu, select

  1. “External interfaces”
  2. “Analogue input (AI1) function” or “Analogue input (AI2) function”
  3. “Select the sensor position”.

The following positions are available:

  • Internal sensor
  • Analogue input 1
  • Analogue input 2
  • BMS
  • Feed
  • Return
  • Primary circuit 1
  • Primary circuit 2
  • Secondary circuit 1
  • Secondary circuit 2
  • Accumulator
  • Hall
  • Circulation