SSM/SBM relay forced control
A SSM/SBM relay forced control is used as function test of the SSM/SBM relay and electrical connections.
In the “Diagnostics and measured values” menu , select
- “Diagnostics help”
- “SSM relay forced control” or “SBM relay forced control” in sequence.
Selection options:
SSM/SBM relay Forced control | Help text |
---|---|
Normal | SSM: Depending on the SSM configuration, fault and warnings influence the SSM relay switching status. SBM: Depending on the SBM configuration, the pump status influences the SBM relay switching status. |
Forced active | SSM/SBM relay switching status is forced ACTIVE. ATTENTION: |
Forced inactive | SSM/SBM relay switching status is forced INACTIVE. ATTENTION: |
With the “Forced active” setting, the relay is permanently activated so that a warning/operational indicator (lights) are displayed/signalled continuously.
With the “Forced inactive” setting, the relay is permanently without signal so that there is no confirmation of a warning/operational signal.