SSM/SBM relay forced control

A SSM/SBM relay forced control is used as function test of the SSM/SBM relay and electrical connections.

In the “Diagnostics and measured values” menu , select

  1. “Diagnostics help”
  2. “SSM relay forced control” or “SBM relay forced control” in sequence.

Selection options:

Selection option SSM/SBM relay forced control

SSM/SBM relay

Forced control

Help text

Normal

SSM: Depending on the SSM configuration, fault and warnings influence the SSM relay switching status.

SBM: Depending on the SBM configuration, the pump status influences the SBM relay switching status.

Forced active

SSM/SBM relay switching status is forced ACTIVE.

ATTENTION:
SSM/SBM does not show the pump status!

Forced inactive

SSM/SBM relay switching status is forced INACTIVE.

ATTENTION:
SSM/SBM does not show the pump status!

With the “Forced active” setting, the relay is permanently activated so that a warning/operational indicator (lights) are displayed/signalled continuously.

With the “Forced inactive” setting, the relay is permanently without signal so that there is no confirmation of a warning/operational signal.