Pump kick

In order to prevent blocking of the pump, a pump kick is set on the pump. After a set time interval, the pump starts and switches off after a short time.

Prerequisite:

For the pump kick function, the mains voltage must not be interrupted.

CAUTION

Blockage of the pump due to long downtimes!

Long downtimes may lead to blockage of the pump. Do not deactivate pump kick!

Pumps switched off through remote operation, bus command, control input External OFF or 0 – 10 V signal run for a short time at least every 24 hours. This prevents blockage after long downtimes.

In the “Settings” menu, select

  1. “Device settings”
  2. “Pump kick”
  • to set the time interval for the pump kick between 1 and 24 hours (factory setting: 24 h).
  • to switch the pump kick on and off.

NOTICE

When it is planned to switch off the mains voltage for a longer period of time, the pump kick must be performed using an external control by switching on the mains voltage briefly.

For this purpose, the pump must be switched on by the controller before the power supply is interrupted.