Adjustment - Manual operation

All control modes, which are selected via the settings assistant, can be overridden with the functions of manual operation OFF, MIN, MAX, MANUAL.

Functions of manual operation can be selected in menu “Settings” “Manual operation”
“Manual operation (OFF, MIN, MAX, MANUAL)”:

Functions of manual operation

Function

Description

Auto control mode

Pump works according to the set controls.

OFF

Pump is switched off. Pump is not running.
All other set controls will be overridden.

MIN

Pump is set to minimum power.
All other set controls will be overridden.

MAX

Pump is set to maximum power.
All other set controls will be overridden.

MANUAL

Pump is working according to set control, which is meant for the “MANUAL” function.

The functions of manual operation OFF, MAX, MIN, MANUAL correspond to the functions Ext. OFF, Ext. MAX, Ext. MIN and Ext. MANUAL.
Ext. OFF, Ext. MAX, Ext. MIN and Ext. MANUAL can be triggered through the digital inputs or through a bus system.

Priorities

Priorities

Priority*

Function

1

OFF, Ext. OFF (binary input), Ext. OFF (bus system)

2

MAX, Ext. MAX (binary input), Ext. MAX (bus system)

3

MIN, Ext. MIN (binary input), Ext. MIN (bus system)

4

MANUAL, Ext. MANUAL (binary input)

* Priority 1 = highest priority

NOTICE

The “MANUAL” function replaces all functions including those which are controlled via a bus system.

If a monitored bus communication fails, the control mode set through the “MANUAL” function is activated. (Bus Command Timer)

Adjustable control modes for the MANUAL function:

Control modes MANUAL function

Control mode

MANUAL – Differential pressure Δp-c

MANUAL – Differential pressure Δp-v

MANUAL – Volume flow Q-const

MANUAL – Speed n-const