Preparing the installation

  1. Attach pipes to the floor, ceiling or wall using appropriate fittings so that the pump does not bear the weight of the piping.
  2. Branch off the safety feed ahead of the pump when installing in feed of open systems (EN 12828).
  3. Install the pump at an easily accessible point so that it can be easily checked or replaced at a later time.
  4. Complete all welding and soldering processes.
  5. Flush unit.
  6. Provide shut-off devices upstream and downstream of the pump.
  7. Comply with the inlet and outlet sections in front of and behind the pump.
  8. Make sure that the pump can be installed free of mechanical stresses.
  9. Allow a 10 cm distance around the control module so that it does not overheat.
  10. Observe permissible installation positions.

Installation within a building

The pump should be installed in a dry, well ventilated and dust-free room – in accordance with the protection class (see rating plate of the pump).

CAUTION

Exceeding/dropping below the permissible ambient temperature!

The control module switches off in the event of excess temperatures!

  • Provide adequate ventilation/heating!
  • Do not cover the control module and pump with objects!
  • Provide a clearance of min. 10 cm around the control module!
  • Ambient temperatures below -10 °C are not permitted!

Installation outside a building (outdoor installation)

  • Observe permissible environmental conditions and protection class.
  • Install the pump in a housing as weather protection. Ambient temperatures below -10 °C are not permitted.
  • Protect the pump against the effects of weather such as direct sunlight, rain and snow.
  • Protect the pump so that the condensate drain openings remain free of dirt.
  • Implement suitable measures to prevent the formation of condensation water.