Technical data
Technical data for heating/air conditioning/cooling
![Technical data for heating/air conditioning/cooling](../Images/jpg/191054091__Web.jpg)
Technical data | |
---|---|
Permissible fluid temperature | -10 to +110 °C |
Permitted ambient temperature | -10 to +40 °C |
Maximum relative humidity | 95 % (non-condensing) |
Mains voltage | 1~ 230 V +/-10 % 50/60 Hz |
Residual current ∆I | ≤ 3.5 mA |
Electromagnetic compatibility | Emitted interference in acc. with: EN 61800-3:2004+A1:2012 / residential environment (C1) Interference resistance in acc. with: EN 61800-3:2004+A1:2012 / industrial environment (C2) |
Emissions-sound-pressure level | < 54 dB(A) |
Energy efficiency index (EEI)* | ≤ 0.17 to ≤ 0.19 (depends on type) |
Temperature class | TF110 (see IEC60335-2-51) |
Pollution degree | 2 (IEC 60664-1) |
Max. permitted operating pressure | PN 6/10 1), PN 16 2) |
*EEI value of the pump is achieved when the display is switched off. 1) Standard version 2) Special version or auxiliary equipment (at additional charge) |
Technical data for drinking water
![Technical data for drinking water](../Images/jpg/191057419__Web.jpg)
Technical data | |
---|---|
Permissible fluid temperature | 0 to +80 °C |
Permitted ambient temperature | 0 to +40 °C |
Maximum relative humidity | 95 % (non-condensing) |
Mains voltage | 1~ 230 V +/-10 % 50/60 Hz |
Residual current ∆I | ≤ 3.5 mA |
Electromagnetic compatibility | Emitted interference in acc. with: EN 61800-3:2004+A1:2012 / residential environment (C1) Interference resistance in acc. with: EN 61800-3:2004+A1:2012 / industrial environment (C2) |
Emissions-sound-pressure level | < 54 dB(A) |
Energy efficiency index (EEI)* | ≤ 0.17 to ≤ 0.19 (depends on type) |
Temperature class | TF110 (see IEC60335-2-51) |
Pollution degree | 2 (IEC 60664-1) |
Max. permitted operating pressure | PN 6/10 1), PN 16 2) |
*EEI value of the pump is achieved when the display is switched off. 1) Standard version 2) Special version or auxiliary equipment (at additional charge) |
For further instructions see rating plate and catalogue.