Technical data

Technical data for heating/air conditioning/cooling

Technical data for heating/air conditioning/cooling
Technical data for heating/air conditioning/cooling
Technical data for heating/air conditioning/cooling

Technical data

Permissible fluid temperature

-10 to +110 °C

Permitted ambient temperature

-10 to +40 °C

Maximum relative humidity

95 % (non-condensing)

Mains voltage

1~ 230 V +/-10 % 50/60 Hz

Residual current ∆I

≤ 3.5 mA

Electromagnetic compatibility

Emitted interference in acc. with:

EN 61800-3:2004+A1:2012 / residential environment (C1)

Interference resistance in acc. with:

EN 61800-3:2004+A1:2012 / industrial environment (C2)

Emissions-sound-pressure level

< 54 dB(A)

Energy efficiency index (EEI)*

≤ 0.17 to ≤ 0.19 (depends on type)

Temperature class

TF110 (see IEC60335-2-51)

Pollution degree

2 (IEC 60664-1)

Max. permitted operating pressure

PN 6/10 1), PN 16 2)

*EEI value of the pump is achieved when the display is switched off.

1) Standard version

2) Special version or auxiliary equipment (at additional charge)

Technical data for drinking water

Technical data for drinking water
Technical data for drinking water
Technical data for drinking water

Technical data

Permissible fluid temperature

0 to +80 °C

Permitted ambient temperature

0 to +40 °C

Maximum relative humidity

95 % (non-condensing)

Mains voltage

1~ 230 V +/-10 % 50/60 Hz

Residual current ∆I

≤ 3.5 mA

Electromagnetic compatibility

Emitted interference in acc. with:

EN 61800-3:2004+A1:2012 / residential environment (C1)

Interference resistance in acc. with:

EN 61800-3:2004+A1:2012 / industrial environment (C2)

Emissions-sound-pressure level

< 54 dB(A)

Energy efficiency index (EEI)*

≤ 0.17 to ≤ 0.19 (depends on type)

Temperature class

TF110 (see IEC60335-2-51)

Pollution degree

2 (IEC 60664-1)

Max. permitted operating pressure

PN 6/10 1), PN 16 2)

*EEI value of the pump is achieved when the display is switched off.

1) Standard version

2) Special version or auxiliary equipment (at additional charge)

For further instructions see rating plate and catalogue.